Vue de la page 52
51
COMPACT
®
NS circuit breaker
E28287
Reflex tripping
All COMPACT
®
NS circuit breakers and switches incorporate the exclusive reflex
tripping system.
This extremely simple system breaks very high fault currents by mechanically
tripping the device via a "piston" actuated directly by the pressure produced in the
breaking units resulting from a short circuit.
For high short-circuit thermal withstand, this system provides a faster break.
Reflex tripping curves are exclusively a function of the circuit breaker rating.
Trip curves
COMPACT
®
NS circuit breaker: supplementary technical information
5
20
10
8
7
6
4
3
2 3 4 6 10 20 30 40 60 100 200
t
(ms)
NSJ600
NSJ400
NSF250
NSF150
TM70DP…TM250DP
TM15DP...TM60DP
I (kA RMS)